Product

best technology and service

Honeywell Sensepoint XCD

The Sensepoint XCD range provides comprehensive monitoring of flammable, toxic and Oxygen gas hazards in potentially explosive atmospheres, both indoors and outdoors.
Users can modify detector operation using the LCD and magnet switches without ever needing to open the unit.
This enables one-man, non-intrusive operation and reduces routine maintenance time and costs.
DATA SHEET DOWNLOAD

FEATURES AND BENEFITS

  • 01. Flammable (catalytic or infrared), toxic and oxygen versions available
  • 02. Stainless steel or aluminium explosion-proof housing options
  • 03. User friendly and intuitive tri-color backlit display with digits, bar graph and icons
  • 04. MODBUS communications for remote diagnostics/configuration

SPECIFICATION

Classification criteria classification
Input Voltage Range 12 to 32VDC (24VDC nominal)
Max Power Consumption Maximum power consumption is dependent on the type of gas sensor being used.
Electrochemical cells = 3.7W, IR = 3.7W and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC
Current Output Relays Sink or source
Relays 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energized/de-energised (programmable) Alarm relays default normally open/de-energized. Fault relay default normally open/energized
Communication RS485, MODBUS RTU
Material Housing: Epoxy painted aluminium alloy ADC12 or 316 stainless stee
Sensor: 316 stainless steel
Weight (approx) Aluminium Alloy LM25: 4.4lbs
316 Stainless Steel: 11lbs
Mounting Integral mounting plate with 4 x mounting holes suitable for M8 bolts. Optional pipe mounting kit for horizontal or vertical pipe Ø1.5 to 3" (2" nominal)
Cable Entries UL\cUL versions: 2 x ¾”NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating; ATEX/IECEx versions: 2 x M20 cable entries
IP Rating IP66 in accordance with EN60529:1992
Certified Temperature Range -40 ~ 149ºF (-40 ~ 65ºC)
Certifications ATEX - Ex II 2 GD
- Ex d IIC Gb T6 (Ta -40ºC to +65ºC)
- Ex tb IIIC T85°C Db IP66
UL/c-UL Class I,Division 1,Groups B, C and D,
Class I, Division 2, Groups B, C & D,
Class II, Division 1, Groups E, F & G
Class II, Division 2, Groups F & G. -40°C to +65°C
EMC CE: EN50270:2006 EN6100-6-4:2007
Performance UL508; CSA 22.2 No. 152 (flammable gasses, excludes infrared sensors); ATEX, IEC/EN60079-29-1:2007, EN45544, EN50104, EN50271; China: PA Pattern Measurement (for transmitter and toxic gas sensors) “CCCF” Shenyang for Flammable (fire dept approval)

Sensor List

SENSOR Measuring Range
O2 0 - 25.0%Vol.
H2S 0 - 50.0ppm
CO 0 - 300ppm
H2 0 - 1,000ppm
NO2 0 - 10.0ppm
Flammable 0 - 100%LEL
CH4 0 - 100%LEL
C₃H₈ 0 - 100%LEL
CO2 0 - 2%Vol.